| MPM Pressure Indicator/Transmitter with Alarms | |
| DESCRIPTION The MPM family of panel meters incorporates the use of a microprocessor and a solid-state, silicone piezoresistive sensor. The microprocessor allows for no trim pots, all digital calibration and overall product flexibility. The MPM family of panel meters combines an indicator, a switch, and a transmitter, with a large, vibrant 3 1/2 digit LCD display, all in a compact, 1/8 DIN enclosure. On the MPM2, set point settings are easily made by the on-board, push-button adjustments. The MPM family of pressure panel meters features a “zero” adjustment, making mounting orientation flexible and easy — and (on the MPM2) the two on-board LEDs allow for bright visual indication of when a Hi and/or Lo point has been achieved. The MPM family of pressure panel meters may be ordered with dual relays providing for output switching. Typical applications would include those where a Hi and/or a Lo alarm point are important. The MPM family is available with a 2 or 7 amp failsafe configured relay. Models with relays also feature an easy-to-use, programmable deadband, which can be set for up to 25% of the range of the unit, in .100% increments. Relative accuracy is 0.5% of full range. The unit is fully compatible with air and other inert gases. Ranges are available up to 20" WCD and 5 kPaD. An optional gasket is available in order to make the faceplate meet NEMA 4 requirements. KEY FEATURES 3 1/2 Digit LCD Display All models have a 31/2 digit LCD display. Also the use of a membrane style keypad makes wipe down very easy. Analog Outputs/Hi-Lo Relay Set Points On certain models, a 4-20 mA or 0-5 vdc Analog output are available. Also, on certain models a hi and lo relay set point may be set by utilizing the “Mode” keypad button, as well as the “up arrow” keypad button. It allows you to easily scroll through the 31/2 digit display to arrive at a desired pressure set point. |
![]() APPLICATIONS HVAC Applications Filter Monitoring Flow Monitoring Fan Static Pressure Draft Pressures Room Pressurization Industrial Applications Fume Hoods Paint Spray Booth Filters Bubbler Level Systems Boiler (Draft) Pressures Pollution Control Equipment (Baghouses) HEPA Filter Monitoring (pharmaceutical and semiconductor plants) |
![]() |
|
| SPECIFICATIONS | |
| Dimensions | 1/8 DIN, 1.66" deep (from base of pressure fittings) |
Display | 3 1/2 digit LCD display |
| Panel Cutout Dimensions | 3.62" wide x 1.77" high | Power Requirements | 5 to 36 VDC for models without outputs 11 to 36 VDC for models with 4-20 mA 5 to 13 VDC or 12 to 32 VDC with Relay option. |
| Material | ABS Plastic ULV94V-1 | Power Consumption | 30 mA for models without Relays (typ. < 1 watt) 100 mA for models with relays or Analog outputs 200 mA for models with relays and Analog outputs |
| Enclosure | NEMA 4/IP 65 (front panel only) with gasket accessory |
Pressure Line Polarity | automatically bi-directional |
| Measurement Ranges Available | ±2" WCD ±5" WCD ±10" WCD ±20" WCD ±2 kPa ±5 kPa (all units are bi-directional) |
Warm-up Time | 3 minutes to rated accuracy |
| Proof Pressure | 3x Range | Connections – | Electrical Power – screw terminal, 14-26 AWG Outputs – screw terminal, 16-28 AWG |
| Operating Temperature Range | 0 to 55°C | Pressure Lines 1/8 NPT (Female) |
|
| Storage Temperature Range | -20 to 70°C | Outputs (optional) | Analog output (4-20 mA and 0-5 VDC) Dual Relay Contacts, 2 Amp, SPDT Dual Relay Contacts, 7 Amp, SPDT |
| Relative Humidity | 10% to 90% | User Adjustments | Three push-buttons (Zero, Mode Selection, Up-Arrow) Set Points Deadband Analog Output Offsets |
| Relative Accuracy | ±0.5% | ||
| Span Tempco | ±0.02%/°C | ||
| Zero Tempco | ±0.05%/°C | ||
ORDERING INFORMATION![]() |
Order Number
(See Table below) MPM-Model-Options-Additional Features D-M-R-O-AF EXAMPLE: MPM-1-06EB-R7-N |
||
| Description (one choice only) |
Model (one choice only) |
Range (one choice only) |
Options (one choice only) |
Additional Features |
| MPM | 1 = Base
Model Basic product with 3-1/2 digit LCD display. Pushbutton Zero. 1/8 DIN case. 5 to 36 VDC power input. See Note 1 |
06EB =
+/-2" wcd |
R2 = 2 alarm relays; high and low; 11-32
VDC; contact rating of 2 amps; user programmable deadband up to 25%
of range. Available on ALL MPM2 Models. |
N = NEMA 4 Gasket Available on all models. |
| 2 = Enhanced
Model Basic product
(MPM1) with front panel Hi and Lo alarm LED indicators and Hi/Lo alarm
(setpoint) capability. Mode and +/- front panel buttons added. See Note 2 |
08EB = +/- 5" wcd | R7 = 2 alarm
relays; high and low; 11-32 VDC; contact rating of 7 amps; user programmable
deadband up to 25% of range. Available on ALL MPM2 Models |
||
| 09EB = +/- 10" wcd | AO = isolated
4-20mA, 3-wire current loop output and 0-5 VDC output. |
|||
| 11EB = +/- 20" wcd | R2AO = R2 and AO
combined |
|||
| 09PB = +/- 2 kPaD | R7AO = R7 and AO
combined |
|||
| 11PB = +/- 5 kPaD | ||||
| Note 1: All models without option boards are 5-36 VDC; all option boards are 11-32 VDC | ||||
| Note 1: All items in Options columns are only available on MPM2 | ||||